Duct heater power calculationformula and worked examples

The standard heat duty formula, airflow unit conversions, how much margin to add — then two real projects calculated end to end.

  • P = ṁ·c·ΔT
  • Convert airflow units first
  • Margin: 10–20%
  • Stage the heater banks

Duct HeatingPublished 2026-09-11中文版 ↗

01The standard formula

Air (and most flue or process gases) has a specific heat of about 1.01 kJ/(kg·°C). The duty formula is: P = ṁ × c × ΔT / 3600, where ṁ is mass flow in kg/h, c = 1.01 kJ/(kg·°C), ΔT the temperature rise in °C, and 3600 converts kJ/h into kW.

A handy mental constant: at standard conditions, every 1,000 m³/h of air needs roughly 0.33 kW per °C of temperature rise. With that number you can sanity-check any quotation on the spot.

02The classic mistake: airflow units

Process documents usually quote actual (operating) m³/h — volume at the real duct temperature. The formula needs mass flow, so convert first: ṁ = qv × ρ, with ρ taken at the actual temperature. 10,000 m³/h of hot air can carry 30% less mass than the same number at ambient — mixing up the two skews the result by exactly that much.

The second trap is leakage and fluctuation: negative-pressure sections pull in extra air, and fan flow shifts with system resistance. If the airflow number is wrong, no amount of formula precision saves the answer — verify against the fan's actual operating point.

03How much margin

Add 10–20% on top of the theoretical duty: the high end for poor insulation, frequent starts or fluctuating inlet temperatures, the low end for stable continuous duty with well-defined airflow. Oversizing is not free — an oversized heater running at low turndown controls worse and wastes both capital and transformer capacity.

For large airflows and high temperature rises, split the heater into 2–4 staged banks: energize sequentially at start-up to avoid grid inrush, then combine stages as needed for steady, precise outlet control.

04Example 1: process drying air

Duty: 8,000 m³/h recirculating at 80°C (ρ ≈ 1.0 kg/m³), returning air at 60°C, supply at 120°C → ΔT = 60°C. Mass flow = 8,000 × 1.0 = 8,000 kg/h. P = 8,000 × 1.01 × 60 / 3600 ≈ 134.7 kW. With 15% margin, specify roughly 155 kW in three staged banks.

05Example 2: exhaust preheat ahead of RTO

Duty: 20,000 m³/h exhaust at 100°C (ρ ≈ 0.95 kg/m³), preheated from 25°C to 320°C → ΔT = 295°C. Mass flow = 19,000 kg/h. P = 19,000 × 1.01 × 295 / 3600 ≈ 1,570 kW. At this scale, electric heating duty warrants a review of available grid capacity — staged multi-level heating or a primary heat source (steam/thermal oil) with electric trim is often the better architecture. With VOC-laden streams, also verify element surface temperatures against the medium's safety margin.

Send us the numbers — we'll run them through this method

Medium, flow, temperatures, pressure. With those four, duty and architecture are a same-day answer.

Submit your duty →

FAQ

Frequently asked

01The datasheet quotes Nm³/h — how do I convert?+

Nm³/h is standard volume flow. Multiply by standard density (~1.29 kg/m³) to get mass flow directly; no temperature correction needed. Just be sure which basis the document actually uses.

02The result is a non-standard kW rating — now what?+

Electric heaters are built to order, so round to the nearest sensible rating with margin, or use staged banks for multi-step output. Exact-value matching is unnecessary.

03What density should I use for hot air?+

At atmospheric pressure roughly: 0.95 kg/m³ at 100°C, 0.75 at 200°C, 0.62 at 300°C. Close enough for sizing; correct for pressure when precision matters.

INQUIRY PREP

Come prepared, decide faster on Duct Heating

Have these parameters ready — they feed directly into model selection, power sizing and mechanical design review.
Send your spec ↗
K13Electric heaters for paint curing and powder coating ovensHow to size an electric heater for a paint curing or powder coating oven: the four real loads, a worked tunnel example, element layout in recirculating air, and the three commissioning failures that get blamed on the heater.K20Electric reheat for cleanroom and pharmaceutical AHUsElectric reheat in cleanroom and pharmaceutical air handling: duty from airflow and ΔT, hygienic element construction, face velocity limits, SCR versus stepped control, and the interlocks and documentation a validated plant expects.K17Electric heaters for nitrogen and other inert gasesSizing electric heaters for nitrogen, argon and other inert gases: mass flow and cp arithmetic, a worked superheat example, why small kW still means high sheath temperature, velocity and pressure effects, and the interlocks.K10How should a duct heater interlock with the fan?Four duct-heater interlock rules, the airflow and temperature rise power formula, inlet-side probe errors, and why an independent high-limit trip is needed.K7What watt density should an electric heater tube use?How to calculate watt density, the working ranges for water, oil, still air and forced air, and the four mistakes that burn tubes: total power only, heated length, scaling and supply voltage.K12Why is my heater underperforming when the calculation was fine?Four causes behind low output: supply voltage, insulation loss, flow off the design point and fouling or a dead bank — plus the U² power relation and a four-step site test.K9What protection settings does an electric thermal oil heater need?The four guards on electric thermal oil heaters — outlet high limit, low level, loss of circulation and sheath over-temperature — their action order, why film temperature governs, and typical missettings.K1Why thermal oil heaters coke up — and how to prevent itCoking is not an oil problem. It is what happens when surface heat flux, flow velocity and film temperature get out of balance — here is how to keep them in line.K3Hazardous-area electric heaters: Group IIB/IIC and temperature class explainedHigher Ex rating is not automatically safer — it is about matching. Zone, gas group and temperature class, one layer at a time.K4Five installation mistakes that ruin pipeline heatersThe heater was fine; the installation set the trap. Reverse flow, misplaced sensors, no minimum-flow interlock, pipe stress on flanges, missing vents — check your site against this list.K5Why tubular heater elements fail early: sheath material and watt densityTwo 220V 3kW elements — one lasts three years, one lasts three months. The difference is sheath alloy, watt density, medium match and termination quality.K6Electric heating duty calculation: from specific heat to a real specificationThis guide covers the heat-duty formula, common property values, additional loads and the process data needed for a preliminary quotation.