Calculated power, weak output on site: four checks to run

The gap between drawing and site is rarely the formula. It is supply voltage, heat loss through insulation, actual flow and fouling — all measurable with instruments in an afternoon.

  • Measure phase current first
  • Check voltage on load
  • Back-calculate from ΔT and flow
  • Scan insulation with IR

Heater sizingPublished 2026-10-08中文版 ↗

01Four real causes

Supply below rated voltage

Output follows the square of voltage. At 340 V a 380 V rated heater delivers roughly 80% of its nameplate power.

Underestimated heat loss

Missing or thin insulation, plus steelwork bridging, can consume the whole design margin.

Flow away from design point

A pump or fan working somewhere else on its curve changes the duty: more medium flow, smaller temperature rise — it feels underpowered.

Fouling or a dead bank

Scale on the water side, carbon on the oil side, dust on the air side; or one control bank that never picks up.

02Voltage against output

P actual / P rated = (U actual / U rated)². End-of-line voltage drop, transformer tap position and a sagging summer grid can take 5%~10% off supply, which is 10%~19% off output. If the calculation used rated voltage while the site runs at 340~360 V, the shortfall is explained there — and with a long cable run, check the drop at the heater terminals, not at the panel.

On the loss side, thickness per the specification is not the end of it: scan the outer surface with infrared. Anywhere noticeably warmer than ambient is exporting heat. Steelwork, supports and nozzle penetrations often matter more than the insulation thickness itself.

03The four-step site order

Current

Clamp-meter each phase and compare with nameplate amps. One phase clearly low means that group is not energised.

Voltage on load

Record terminal voltage while running. No-load voltage proving fine tells you nothing.

ΔT and flow

Back-calculate the power absorbed by the medium from measured rise and flow, then compare with theoretical output.

Insulation

Walk an IR camera over the lagging and at brackets, nozzles and wall penetrations. Hot spots are heat escaping.

04Two things to re-check after the maths

Re-check two points: whether the design assumed continuous running while production is actually intermittent (cold starts need extra duty), and whether the control allows staged switching, so the plant is not paying for peak capacity at part load most of the time. Most underperforming sites end up fixed on run pattern and heat loss, not on the heater rating.

↗Related reading

Can a 400V Heater Run on a 480V Supply?

Send the numbers and we will run them through this method

Medium, flow, temperatures, pressure. With those four, duty and architecture are a same-day answer.

Submit your duty →

FAQ

Common questions

01Brand-new plant and already weak output?+

Start with phase current and voltage on load. A single-phased termination and a control bank that never closes account for most new-install cases.

02Output drifting down over the years?+

Water side: scale. Oil side: carbon layer. Air side: dust and reduced airflow. All three stop the same power reaching the medium.

03Can I just raise the setpoint?+

No — that changes the target, not the capacity. The result is a longer ramp and a hotter sheath.

INQUIRY PREP

Come prepared, decide faster on Tubular Elements

Have these parameters ready — they feed directly into model selection, power sizing and mechanical design review.
Send your spec ↗
K21Electric or gas heating for an industrial drying line?A practical comparison of electric and gas heating for industrial drying lines: installed cost, permits, turndown, response, combustion moisture, demand charges and standby — with the arithmetic to run on your own tariff.K19Electric heating for CIP wash water and clean tanksElectric heating for CIP and wash-water tanks: kW from volume and recovery time, sheath material against caustic, acid and chlorine, watt density in tank duty, and surviving the drained phase between cycles.K7What watt density should an electric heater tube use?How to calculate watt density, the working ranges for water, oil, still air and forced air, and the four mistakes that burn tubes: total power only, heated length, scaling and supply voltage.K8How to support a pipeline heater and allow for expansion?Bracket layout for pipeline heaters, expansion growth by material, why both-ends-fixed joints leak, and the cold-plus-hot commissioning checks.K9What protection settings does an electric thermal oil heater need?The four guards on electric thermal oil heaters — outlet high limit, low level, loss of circulation and sheath over-temperature — their action order, why film temperature governs, and typical missettings.K10How should a duct heater interlock with the fan?Four duct-heater interlock rules, the airflow and temperature rise power formula, inlet-side probe errors, and why an independent high-limit trip is needed.K11How to pick the temperature class for an Ex heater?T1 to T6 surface limits, why peak temperature includes fault conditions, the margin needed for control swing and probe placement, and four installation checks on flame paths and glands.K1Why thermal oil heaters coke up — and how to prevent itCoking is not an oil problem. It is what happens when surface heat flux, flow velocity and film temperature get out of balance — here is how to keep them in line.K2Duct heater power calculation — formula and worked examplesThe standard heat duty formula, airflow unit conversions, how much margin to add — then two real projects calculated end to end.K3Hazardous-area electric heaters: Group IIB/IIC and temperature class explainedHigher Ex rating is not automatically safer — it is about matching. Zone, gas group and temperature class, one layer at a time.K4Five installation mistakes that ruin pipeline heatersThe heater was fine; the installation set the trap. Reverse flow, misplaced sensors, no minimum-flow interlock, pipe stress on flanges, missing vents — check your site against this list.K6Electric heating duty calculation: from specific heat to a real specificationThis guide covers the heat-duty formula, common property values, additional loads and the process data needed for a preliminary quotation.